![ABB ACQ810 Firmware Manual Download Page 269](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549269.webp)
Parameters 269
80.07
HQ curve H2
Head (in meters) at point 2 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 2 of the HQ curve.
100 = 1 m
80.08
HQ curve Q3
Flow rate (in cubic meters per hour) at point 3 of the HQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 3 of the HQ curve.
100 = 1 m
3
/h
80.09
HQ curve H3
Head (in meters) at point 3 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 3 of the HQ curve.
100 = 1 m
80.10
HQ curve Q4
Flow rate (in cubic meters per hour) at point 4 of the HQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 4 of the HQ curve.
100 = 1 m
3
/h
80.11
HQ curve H4
Head (in meters) at point 4 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 4 of the HQ curve.
100 = 1 m
80.12
HQ curve Q5
Flow rate (in cubic meters per hour) at point 5 of the HQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 5 of the HQ curve.
100 = 1 m
3
/h
80.13
HQ curve H5
Head (in meters) at point 5 of the HQ performance curve.
0.00 … 32767.00 m
Head at point 5 of the HQ curve.
100 = 1 m
80.14
PQ curve P1
Power input (in kilowatts) of pump at point 1 on the PQ
performance curve.
Parameters
…
define the PQ performance curve
of the pump for the flow calculation function. The P (power
input) and Q (flow rate) coordinates of five points on the
curve are entered. The values are provided by the pump
manufacturer. All points defined should lie within the
practical operating range of the pump.
Below is an example of an PQ performance curve. The
defining parameters of the first and last points are shown.
0.00 … 32767.00
kW
Power input of pump at point 1.
100 = 1 kW
No.
Name/Value
Description
FbEq
P [kW]
Q [m
3
/h]
2
4
5
3
1
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...