Parameters 221
Moderate
Flux level is limited during the braking. Deceleration time is
longer compared to full braking.
1
Full
Maximum braking power. Almost all available current is used
to convert the mechanical braking energy to thermal energy
in the motor.
2
44
44 Maintenance
Maintenance counter configuration.
See also section
on page
44.01
Ontime1 func
Configures on-time counter 1. This counter runs whenever
the signal selected by parameter
is on.
After the limit set by parameter
is
reached, an alarm specified by parameter
is given, and the counter reset.
The current value of the counter is readable from parameter
. Bit 0 of
indicates that the count has exceeded the limit.
44.02
Ontime1 src
Selects the signal to be monitored by on-time counter 1. See
parameter
RO1
Relay output RO1 (as indicated by
, bit 0).
1073742338
Running
(see page
).
1073939969
Charged
(see page
).
1074333186
Const
Bit pointer setting (see
on page
-
Pointer
44.03
Ontime1 limit
Sets the alarm limit for on-time counter 1. See parameter
.
0…2147483647 s
Alarm limit for on-time counter 1.
44.04
Ontime1 alm sel
Selects the alarm for on-time counter 1. See parameter
.
On-time1
Pre-selectable alarm for on-time counter 1.
0
Device clean
Pre-selectable alarm for on-time counter 1.
1
Add cool fan
Pre-selectable alarm for on-time counter 1.
2
Cabinet fan
Pre-selectable alarm for on-time counter 1.
3
Dc-capacitor
Pre-selectable alarm for on-time counter 1.
4
Mot bearing
Pre-selectable alarm for on-time counter 1.
5
No.
Name/Value
Description
FbEq
Bit
Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...