188 Parameters
27.13
PID integ time
Defines the integration time for the process PID controller.
0.00 … 320.00 s
Integration time.
100 = 1 s
27.14
PID deriv time
Defines the derivation time of the process PID controller. The
derivative component at the controller output is calculated on
basis of two consecutive error values (E
K-1
and E
K
)
according to the following formula:
PID DERIV TIME × (E
K
- E
K-1
)/T
S
, in which
T
S
= 12 ms sample time
E = Error = Process setpoint - process actual value.
0.00 … 10.00 s
Derivation time.
100 = 1 s
27.15
PID deriv filter
Defines the time constant of the 1-pole filter used to smooth
the derivative component of the process PID controller.
0.00 … 10.00 s
Filter time constant.
100 = 1 s
No.
Name/Value
Description
FbEq
Ti
O
I
G × I
G × I
I = controller input (error)
O = controller output
G = gain
Ti = integration time
Time
Error/Controller output
63
%
100
T
t
O = I × (1 - e
-t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...