![ABB ACQ810 Firmware Manual Download Page 165](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549165.webp)
Parameters 165
16.09
User set sel
Enables the saving and restoring of up to four custom sets of
parameter settings.
The set that was in use before powering down the drive is in
use after the next power-up.
Notes:
• Fieldbus adapter parameters (groups 50…53) are not part
of user parameter sets.
• Any parameter changes made after loading a set are not
automatically stored – they must be saved using this
parameter.
No request
Load or save operation complete; normal operation.
1
Load set 1
Load user parameter set 1.
2
Load set 2
Load user parameter set 2.
3
Load set 3
Load user parameter set 3.
4
Load set 4
Load user parameter set 4.
5
Save set 1
Save user parameter set 1.
6
Save set 2
Save user parameter set 2.
7
Save set 3
Save user parameter set 3.
8
Save set 4
Save user parameter set 4.
9
IO mode
Load user parameter set using parameters
and
10
16.10
User set log
Shows the status of the user parameter sets (see parameter
). Read-only.
N/A
No user sets have been saved.
0
Loading
A user set is being loaded.
1
Saving
A user set is being saved.
2
Faulted
Invalid or empty parameter set.
4
Set1 IO act
User parameter set 1 has been selected by parameters
and
8
Set2 IO act
User parameter set 2 has been selected by parameters
and
16
Set3 IO act
User parameter set 3 has been selected by parameters
and
32
Set4 IO act
User parameter set 4 has been selected by parameters
and
64
Set1 par act
User parameter set 1 has been loaded using parameter
128
Set2 par act
User parameter set 2 has been loaded using parameter
256
Set3 par act
User parameter set 3 has been loaded using parameter
512
Set4 par act
User parameter set 4 has been loaded using parameter
1024
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...