Parameters 201
31.13
Mot nom tempRise
Defines the temperature rise of the motor when the motor is
loaded with nominal current. See the motor manufacturer's
recommendations.
The temperature rise value is used by the motor thermal
protection model when parameter
is set
0 … 300 °C
Temperature rise.
1 = 1 °C
31.14
Mot therm time
Defines the thermal time constant for the motor thermal
protection model (i.e. time inside which the temperature has
reached 63% of the nominal temperature). See the motor
manufacturer's recommendations.
The motor thermal protection model is used when parameter
is set to
.
100 … 10000 s
Motor thermal time constant.
1 = 1 s
No.
Name/Value
Description
FbEq
Motor nominal
temperature rise
Temperature
Time
Ambient temperature
100%
63%
100%
Time
Time
Motor thermal time
Motor load
Temperature rise
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...