226 Parameters
44.24
Val count2 func
Configures value counter 2. This counter measures, by
integration, the area below the signal selected by parameter
. When the total area exceeds the limit
set by parameter
, an alarm is given (if
enabled by bit 1 of this parameter).
The signal is sampled at 1-second intervals. Note that the
scaled (see the “FbEq” column at the signal in question)
value of the signal is used.
The current value of the counter is readable from parameter
indicates that the counter has exceeded the limit.
44.25
Val count2 src
Selects the signal to be monitored by value counter 2. See
parameter
.
Speed rpm
).
1073742081
Pointer
Value pointer setting (see
on page
).
-
44.26
Val count2 lim
Sets the alarm limit for value counter 2. See parameter
.
0…2147483647
Alarm limit for value counter 2.
1 = 1
44.27
Val count2 div
Divisor for value counter 2. The value of the monitored signal
is divided by this value before integration.
1…2147483647
Divisor for value counter 2.
1 = 1
44.28
Val cnt2 alm sel
Selects the alarm for value counter 2. See parameter
.
Value2
Pre-selectable alarm for value counter 2.
0
Mot bearing
Pre-selectable alarm for value counter 2.
1
44.29
Fan ontime lim
Sets the limit for the cooling fan on-time counter. The counter
monitors signal
(see page
). When the
signal reaches the limit, alarm
is given.
0.00 … 35791394.11
h
Alarm limit for cooling fan on-time.
1 = 1 min
44.30
Runtime lim
Sets the limit for the drive run-time counter. The counter
monitors signal
(see page
When the signal reaches the limit, the alarm specified by
parameter
is given.
0.00 … 35791394.11
h
Alarm limit for the drive run-time counter.
1 = 1 min
44.31
Runtime alm sel
Selects the alarm for the drive run time counter.
Device clean
Pre-selectable alarm for the drive run time counter.
1
Add cool fan
Pre-selectable alarm for the drive run time counter.
2
Cabinet fan
Pre-selectable alarm for the drive run time counter.
3
No.
Name/Value
Description
FbEq
Bit
Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...