Parameters 275
81.11
AI out hi level
Pressure limit for primary outlet pressure supervision. See
parameter
0.00 … 32767.00
bar
Pressure limit.
100 = 1 bar
81.12
Very high ctrl
Enables the secondary supervision of pump outlet pressure
and selects the action taken when very high outlet pressure
is detected. The selected action is taken only after the
measured pressure has remained above the pressure limit
(
) for longer than the value of
parameter
. See the diagram at
parameter
Note:
With a pressure switch, this parameter has no effect.
Not sel
Secondary outlet pressure supervision not used.
0
Fault
Detection of very high outlet pressure trips the drive.
1
Stop
Detection of very high outlet pressure stops the drive. The
drive will restart if the pressure falls below the limit.
2
81.13
AI out very high
Pressure limit for secondary outlet pressure supervision.
See parameter
.
0.00 … 32767.00
bar
Pressure limit.
100 = 1 bar
81.14
DI status outlet
Selects the digital input for connection of a pressure switch
at the pump outlet. The “normal” state is 1. If the selected
input switches to 0, the action defined by parameter
is taken after the delay set by parameter
expires.
Not used
No pressure switch connected.
1074070017
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
81.15
Outlet ctr dly
Delay for primary and secondary supervision of pump outlet
pressure. See parameter
.
0…600 s
Delay.
1 = 1 s
81.16
Outlet force ref
Pump speed reference for parameter
.
0.0 … 32767.0 rpm
Speed reference.
10 = 1 rpm
81.17
Protect dec time
PID controller ramp-down time for parameter
, selection
.
0…18000 s
PID controller ramp-down time for outlet pressure
supervision.
1 = 1 s
81.18
Flow source sel
Selects an source for flow measurement for
minimum/maximum flow protection. See parameters
.
AI1 scaled
).
1073742341
AI2 scaled
).
1073742343
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...