44.09
Edge count1 func
Configures rising edge counter 1. This counter is
incremented every time the signal selected by parameter
switches on (unless a divisor value is
applied – see parameter
). After the
limit set by parameter
is reached, an
given, and the counter reset.
The current value of the counter is readable from parameter
. Bit 2 of
indicates
that the count has exceeded the limit.
44.10
Edge count1 src
Selects the signal to be monitored by rising edge counter 1.
See parameter
RO1
Relay output RO1 (as indicated by
, bit 0).
1073742338
Running
(see page
).
1073939969
Charged
(see page
).
1074333186
Const
Bit pointer setting (see
on page
-
Pointer
44.11
Edge count1 lim
Sets the alarm limit for rising edge counter 1. See parameter
0 … 2147483647
Alarm limit for rising edge counter 1.
1 = 1
44.12
Edge count1 div
Divisor for rising edge counter 1. Determines how many
rising edges increment the counter by 1.
1 … 2147483647
Divisor for rising edge counter 1.
1 = 1
44.13
Edg cnt1 alm sel
Selects the alarm for rising edge counter 1. See parameter
.
Edge count1
Pre-selectable alarm for rising edge counter 1.
0
Main cntactr
Pre-selectable alarm for rising edge counter 1.
1
Output relay
Pre-selectable alarm for rising edge counter 1.
2
Motor starts
Pre-selectable alarm for rising edge counter 1.
3
Power ups
Pre-selectable alarm for rising edge counter 1.
4
Dc-charge
Pre-selectable alarm for rising edge counter 1.
5
No.
Name/Value
Description
FbEq
Bit
Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...