Parameters 197
30.09
Stall function
Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
• The drive is at stall current limit (
)
, and
• the output frequency is below the level set by parameter
, and
• the conditions above have been valid longer than the time
See section
Stall protection (parameters 30.09…30.12)
page
.
30.10
Stall curr lim
Stall current limit in percent of the nominal current of the
motor. See parameter
0.0 … 1600.0%
Stall current limit.
10 = 1%
30.11
Stall freq hi
Stall frequency limit. See parameter
Note:
Setting the limit below 10 Hz is not recommended.
0.5 … 1000.0 Hz
Stall frequency limit.
10 = 1 Hz
30.12
Stall time
Stall time. See parameter
0 … 3600 s
Stall time.
1 = 1 s
31
31 Motor therm prot
Motor temperature measurement and thermal protection
settings.
31.01
Mot temp1 prot
Selects how the drive reacts when motor overtemperature is
detected by motor thermal protection 1.
No
Motor thermal protection 1 inactive.
0
Alarm
The drive generates alarm
if the temperature exceeds the alarm level defined
by parameter
1
Fault
The drive generates alarm
or trips on fault
if
the temperature exceeds the alarm/fault level defined by
parameter
(whichever is lower).
2
No.
Name/Value
Description
FbEq
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates alarm
upon a stall condition.
2
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on fault
upon a stall condition.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...