![ABB ACQ810 Firmware Manual Download Page 327](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549327.webp)
Fault tracing 327
0302
APPL DIR CREATION
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0303
FPGA CONFIG DIR
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0304
PU RATING ID
(0x5483)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0305
RATING DATABASE
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0306
LICENSING
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0307
DEFAULT FILE
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0308
APPLFILE PAR
(0x6300)
Corrupted application file
Note:
This fault cannot be
reset.
Reload application.
If fault is still active, contact your local
ABB representative.
0309
APPL LOADING
(0x6300)
Corrupted application file
Note:
This fault cannot be
reset.
Reload application.
If fault is still active, contact your local
ABB representative.
0310
USERSET LOAD
(0xFF69)
Loading of user set is not
successfully completed
because:
- requested user set does
not exist
- user set is not compatible
with drive program
- drive has been switched
off during loading.
Reload.
0311
USERSET SAVE
(0xFF69)
User set is not saved
because of memory
corruption.
Check the setting of parameter
If the fault still occurs, contact your local
ABB representative.
0312
UFF OVERSIZE
(0x6300)
UFF file is too big.
Contact your local ABB representative.
0313
UFF EOF
(0x6300)
UFF file structure failure.
Contact your local ABB representative.
0314
TECH LIB INTERFACE
(0x6100)
Incompatible firmware
interface
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0315
RESTORE FILE
(0x630D)
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
0316
DAPS MISMATCH
(0x5484)
Mismatch between JCU
Control Unit firmware and
power unit logic versions.
Contact your local ABB representative.
Code
Fault (fieldbus code),
other information
Cause
What to do
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...