Control through a fieldbus adapter 363
The Control Word and the Status Word
The Control Word (CW) is the principal means of controlling the drive from a fieldbus
system. The Control Word is sent by the fieldbus controller to the drive. The drive
switches between its states according to the bit-coded instructions of the Control
Word.
The Status Word (SW) is a word containing status information, sent by the drive to the
fieldbus controller.
Actual values
Actual values (ACT) are 16/32-bit words containing information on selected
operations of the drive.
FBA communication profile
The FBA communication profile is a state machine model which describes the
general states and state transitions of the drive. The
on page
presents the most important states (including the FBA profile state names). The FBA
Control Word (parameter
– see page
) commands the transitions between
these states and the FBA Status Word (parameter
– see page
) indicates
the status of the drive.
Fieldbus adapter module profile (selected by adapter module parameter) defines how
the control word and status word are transmitted in a system which consists of
fieldbus controller, fieldbus adapter module and drive. With transparent modes,
control word and status word are transmitted without any conversion between the
fieldbus controller and the drive. With other profiles (e.g. PROFIdrive for FPBA-01,
AC/DC drive for FDNA-01, and ABB Drives profile for all fieldbus adapter modules)
fieldbus adapter module converts the fieldbus-specific control word to the FBA
communication profile and status word from FBA communication profile to the
fieldbus-specific status word.
For descriptions of other profiles, see the User’s Manual of the appropriate fieldbus
adapter module.
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...