340 Control through the embedded fieldbus interface
7
RESET
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-
ON INHIBITED
.
Note:
This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Continue normal operation.
8, 9 Reserved.
10 REMOTE_
CMD
1
Fieldbus control enabled.
0
Control word <> 0 or Reference <> 0: Retain last Control
word and Reference.
Control word = 0 and Reference = 0: Fieldbus control
enabled. Reference and deceleration/acceleration ramp
are locked.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2. Effective if control
location is parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control
location is parameterized to be selected from fieldbus.
12
…15
Reserved
Bit
Name
Value
STATE/Description
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...