Parameters 249
75.12
Stop speed 1
Defines the stop speed for auxiliary pump 1.
When the speed of the pump connected directly to the drive
falls below this value and one auxiliary pump is running, the
stop delay counter (see parameter
) is
started. If the speed is still at the same level or lower when
the delay elapses, the first auxiliary pump stops.
The running speed of the drive is increased by
-
after the auxiliary pump stops.
.
0…32767 rpm
Stop speed for auxiliary pump 1.
1 = 1 rpm
75.13
Stop speed 2
Defines the stop speed for auxiliary pump 2. See parameter
0…32767 rpm
Stop speed for auxiliary pump 2.
1 = 1 rpm
75.14
Stop speed 3
Defines the stop speed for auxiliary pump 3. See parameter
0…32767 rpm
Stop speed for auxiliary pump 3.
1 = 1 rpm
75.15
Stop speed 4
Defines the stop speed for auxiliary pump 4. See parameter
0…32767 rpm
Stop speed for auxiliary pump 4.
1 = 1 rpm
75.16
Stop speed 5
Defines the stop speed for auxiliary pump 5. See parameter
0…32767 rpm
Stop speed for auxiliary pump 5.
1 = 1 rpm
75.17
Stop speed 6
Defines the stop speed for auxiliary pump 6. See parameter
0…32767 rpm
Stop speed for auxiliary pump 6.
1 = 1 rpm
75.18
Stop speed 7
Defines the stop speed for auxiliary pump 7. See parameter
0…32767 rpm
Stop speed for auxiliary pump 7.
1 = 1 rpm
75.19
Start delay
Defines a start delay for auxiliary pumps. See parameter
.
0…12600 s
Start delay.
1 = 1 s
75.20
Stop delay
Defines a stop delay for auxiliary pumps. See parameter
.
0…12600 s
Stop delay.
1 = 1 s
75.21
Speed hold on
See diagram at parameter
0…100 s
Speed hold time for auxiliary pump switch-on.
1 = 1 s
75.22
Speed hold off
See diagram at parameter
0…100 s
Speed hold time for auxiliary pump switch-off.
1 = 1 s
75.23
Min pumps allow
Defines the minimum number of pumps that will run
simultaneously.
Note:
The pumps that are kept running will ignore the stop
speeds defined for them by other parameters in this group.
0…8
Minimum number of pumps.
1 = 1
75.24
Max pumps allow
Defines the maximum number of pumps that can be run
simultaneously.
0…8
Maximum number of pumps.
1 = 1
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...