
280 Parameters
82.11
Supervis delay
Delay for signal triggering of the cleaning sequence. See
parameter
.
0…600 s
Cleaning sequence triggering delay.
1 = 1 s
82.12
Trig pointer
Cleaning sequence trigger input selection. See parameter
, bit 6.
Not used
No input selected.
0
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
).
-
Pointer
82.13
Clean max ctrl
Defines the action taken if the maximum number of cleaning
sequences (
) is exceeded within
. Forced
cleanings are disregarded.
Not sel
No action taken.
0
Alarm
The drive generates an alarm,
1
Fault
.
2
82.14
Clean max number
Defines the maximum number of cleaning sequences within
the time set by parameter
.
0…30
Maximum number of cleaning sequences.
1 = 1
82.15
Clean max period
Defines the time (ending now) within which cleaning
sequences are counted.
0.00 … 35791394.11
h
Time within which cleaning sequences are counted.
100 = 1 h
82.16
Clean step acc
Defines the acceleration time from 0 rpm to the step
frequency (parameters
and
0…32767 s
Step acceleration time.
1 = 1 s
82.17
Clean step dec
Defines the deceleration time from the step frequency
(parameters
) to 0 rpm.
0…32767 s
Step deceleration time.
1 = 1 s
83
83 Energy monitoring
Energy consumption monitoring settings.
See also section
on page
.
83.01
Energy mon mode
Enables/disables, and selects the mode of, consumed
energy monitoring.
Not used
Energy monitoring not in use.
0
Limits
The current energy monitoring period is compared to the
consumption limit set by parameter
.
1
Previous
The current energy monitoring period (parameter
) is compared to the previous period (
).
2
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...