Program features 81
Diagnostics
Energy savings calculator
This feature consists of three functionalities:
• An energy optimizer that adjusts the motor flux in such a way that the total
efficiency is maximized
• A counter that monitors used and saved energy by the motor and displays them in
kWh, currency, or volume of CO
2
emission, and
• A load analyzer showing the load profile of the drive (see section
on page
).
Note:
The accuracy of the energy savings calculation is directly dependent on the
accuracy of the reference motor power given in parameter
Settings
(page
Energy consumption monitoring
The control program monitors the energy consumption of the drive and pump, and
provides the consumption during the last 12 calendar months as actual signals.
There is also a comparison function that generates an alarm if the consumption rises
significantly compared to past consumption. The length of a monitoring period is set
by a parameter. The energy consumption within the currently running period is
compared to a parameter-adjustable limit, the previous monitoring period, or the
average of two previous periods. Whenever the consumption within the current
period exceeds the reference by a predefined margin (or tolerance), an alarm is
given.
Settings
(page
Diagnostics
Parameters
(page
).
Signal supervision
Three signals can be selected to be supervised by this function. Whenever the signal
exceeds (or falls below) a predefined limit, a bit of
is activated.
Absolute values can be used.
Settings
(page
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...