Appendix B: ZP3 system maintenance
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
139
&
"
5
#
:
1
"
Menu path
Maintenance > Edit Disabled
Purpose
This menu groups the functions relating to enabling and disabling
points, zones, and outputs.
Point
Enable or disable a point, accept the default point address displayed or
enter the address of the point to be edited. The point address and
current state are displayed. Use the scroll feature to display the next or
previous point to be edited.
Zone
Enable or disable a zone, accept the default zone number displayed or
enter the zone number to be edited. The zone number and status is
displayed. Where the points in a zone are not all set to any one status,
the status is shown as “Various settings”. Use the scroll feature to
display the number of points in the zone and the totals of enabled or
disabled points within the zone.
Extinguish Sys
Enable or disable extinguishing control units. Only valid ECU addresses
are displayed. Use the scroll feature to select the ECU to edit.
Sounders
Enable or disable a sounder output. Only outputs and points declared as
sounders are displayed. Use the scroll feature to select the sounder to
edit.
Note: Compliance with EN 54-2 requires that
ê
å
å
sounders are enabled
or disabled together. From Software version 3.11 onwards, this is
achieved by pressing the Restore Disabled Alarms button, which now
toggles between Disable All Sounders and Enable All Sounders, as
indicated by the Sounders Disabled LED.
Outputs
Enable or disable an I/O-mapped output, accept the default output
address displayed or enter the address of the output to be edited. The
output address and status are displayed. Use the scroll feature to
display the output to be edited.
Remote Alarm
Enable or disable the remote alarm relay (fire brigade) switched outputs.
Both the alarm and fault outputs can be edited in this menu.
&
"
5
5
;
1
"
Menu path
Maintenance > View Disabled
Purpose
This menu is used to view points, zones, or outputs that have been
disabled. An Extinguish System submenu is also provided to limit the
points viewed to extinguishing control units. Once a submenu is chosen,
the first disablement in the category is displayed. Use the scroll feature
to view the next or previous disablement.
Points
Display all points that are set to disabled.
Zones
Display zones that are set to disabled. The zone number of the first
disabled zone and the number of points within the zone are displayed.
Extinguish sys
Display extinguishing control units (ECUs) set to disabled.
Sounders
Display sounders that are set to disabled.
Outputs
Display I/O-mapping outputs set to disabled. The address of the first
disabled output is displayed. Use the scroll feature to view the next or
previous disabled output.
Содержание ZP3
Страница 76: ...Chapter 3 Field wiring 68 ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual...
Страница 112: ...Chapter 5 System configuration 104 ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual...
Страница 162: ...Appendix B ZP3 system maintenance 154 ZP3 Fire Control Panel Installation Commissioning and Maintenance Manual...
Страница 163: ......