Chapter 1: Installation overview
28
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
The Digi One 1A Modem as shown in Figure 20 allows remote dial-in access to
the ZP3 panel for diagnostic purposes.
The Modem communicates to the ZP3 panel via the serial port connector JP3 on
the ZPAB-RS232 board located on the ZP3 panel. Legacy modems were
additionally controlled via a Modem Control Board connected on the panel’s SSB
(serial synchronous bus). See Table 9 below for modem specifications.
5
"
#
!
6
+
4
3
;
0
,
4
&
-
!
m
-
Description
Remote diagnostics modem
Mounting
On the ZP3 accessory plate
Wiring
Via connecting lead to the ZPAB-RS232 board
Power requirements
Connector
Voltage
Two-contact barrel connector
+9 to +30 VDC
-
Ambient temperature
0 to 55°C
Relative humidity
5 to 90% noncondensing
Altitude
0 to 3,658 m
EN 60529 rating
IP00
Dimensions (W × L × H)
83 × 133 × 19 mm
Weight
227g