Chapter 3: Field wiring
62
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
¤
¥
¦
§
¨
©
ª
«
¬
®
¯
¯
®
°
±
¥
¨
©
²
±
³
§
´
µ
®
§
µ
¶
§
µ
·
Contacts can be set to be
normally closed or normally open
via software setup
F
1
0
F9
F3
F2
F5
F6
F1
F8
F7
TB6
FAULT
FIRE
1 2 3 4
The relay contacts are rated for a maximum current of 1 A, and a maximum
voltage of 24 VDC or 100 VAC.
See Figure 46 on page 63. The remote manned centre (RMC) alarm output
sends a fire alarm signal to RMC-routing equipment upon receipt of any fire
alarm. This transmits an alarm to a remote manned centre such as a fire brigade
or a manned control room.
The remote manned centre (RMC) fault output sends a fault alarm signal to
RMC-routing equipment upon occurrence of any panel or system fault. This
transmits a fault signal to a remote manned centre such as a fire brigade, or a
manned control room.