Sensitivity/AVF
There are four sensitivity levels for each point. This option lets you set
the sensitivity of devices using the following options.
Sensitivity point. Enter the point address. The current sensitivity is
displayed, and can be changed. Scroll to select the next point address.
AVF (Fire) point. With alarm verification enabled, smoke must be
present for a period before the sensor gives an alarm. Enter the point
address. The setting (AVF on or off) is displayed, which can be
changed. Scroll to select the next point address.
Note: The AVF setting for a fault condition is global, not individual.
Zones
Allocate Z-loop devices to a zone, or remove devices from a zone. Enter
the zone number. The first point address, and the number of devices in
the zone are displayed. Scroll to view the other point addresses in the
zone. To add a new device to the zone, enter a new point address. To
delete an existing device, display its point address and press F1.
Messages
Create or edit identification messages for each point address. In the edit
mode, the panel keyboard is used. Messages can be up to 40
characters in length. Options are provided to delete messages.
Sounder
Create a list of sensors that are fitted with sounder bases (SAB). A
scrolling, current list is shown. To add a new sensor, enter the point
address. To delete a sounder base entry, press F1.
Detector Test
Enable or disable the self-test function of each sensor. Enter the point
address. The screen indicates whether the self-test is on or off. To edit a
new sensor, enter the address or scroll.
Point Type
Allows the device type at the point address to be defined e.g. heat
sensor, optical smoke sensor, call point, etc. This is an optional field as
the panel normally learns the device type automatically.
AGV Allocation
This allows the point addresses which physically exist between loop
isolators to be defined. This is an optional field as the panel normally
learns the addresses automatically.
The Global Settings > View menu provides a view of the attributes of point
addresses on a zonal basis. Enter a range of zones, for example 1-1, 3-5, or All.
The menu path is: Points > Global Settings > View.
Scroll through the point addresses. The options available for each address are
described in Table 21.
Ê
³
Õ
´
©
É
Ó
¬
¾
®
¥
°
µ
³
º
º
¨
©
·
·
©
·
Þ
¥
©
ß
®
¶
µ
¥
®
°
·
Ç
¶
µ
¥
®
°
×
©
·
»
¨
¥
¶
µ
¥
®
°
Sensor sensitivity
View sensitivity settings of devices
AVF (Alarm Verification Function)
Enabled or disabled
Sounder base
Present or not
Detector self-test
Enabled or disabled