Chapter 2: Installing the ZP3 fire control panel
40
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
The ZP3 fire panel is designed for mounting in an indoor location with a
temperature range of
í
5°C to +40°C, a relative humidity of 95% noncondensing,
and an environment that is dry and free of condensation. The environmental
rating is IP30.
The wiring connection to the extinguishant cylinder actuator is a low
impedance circuit, which can draw up to 1 A during actuation. Make sure that
wiring to the actuator is of sufficient capacity to avoid a voltage loss due to wiring
resistance.
Do not drill, file, or carry out any metalwork on the cabinet with any of
the circuit boards installed in the cabinet. Metal filings will enter the circuit and
may cause severe damage.