Chapter 1: Installation overview
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
25
The ZP3 panel can operate 63 remote display units. The address range for the
RDU is 1 to 63, which allows for up to 63 address options. The RDU is wired to
the panel via the ZP3AB-SCB1 SCB driver board.
Usage: Fit the ZP3AB-SCB1 board to the ZP3 panel using the interface marked
“RDU interface”. Accept devices on the panel. The SCB software stream for the
71910 EN panel is SW72401. Once the SCB driver board has been accepted the
user can view the SCB driver software under Operator > Reports to display.
Configure the SCB online, this defines the number of RDUs that can be
connected to the panel.
Navigate to the following menu:
Setup > System Configuration > Peripheral Comms > RDU/SCBR Online
The address of an RDU may not be higher than the number of RDUs configured
to be to online. If this value is set to 32 then RDUs can be connected with
addresses ranging from one to 32. This number defines the valid RDU address
numbers and not the amount of RDUs connected. All RDUs that have addresses
higher than the number entered for RDUs online will not have control abilities.
If this number is set to 63, the address at the RDU can be set to any address
from 1 through 63. If this number is set to 1, only address 1 can be set on the
RDU unit.
When an RDU is configured as being online, it mimics the panel and also sends
control information back to the panel. To disable the RDU control, remove the
controls enabled jumper fitted to the RDU board. The RDU software stream for
the 71910 EN panel is SW72201. Once the RDU has been accepted the user
can view the RDU software under Operator > Reports to Display. If there are ten
RDUs accepted then this menu will have ten entries for RDUs.
Usage: The number selected on the address switch depends on the number of
RDUs defined online. As stated above, the number entered to define the amount
of RDUs online defines the maximum address number. Address switches 1, 2, 3,
4, 5, and 6 set the address in the standard address switch format as used on the
detectors, e.g. switches 2, 3, 4, 5, and 6 set to ON represent an RDU address of
62.
An accessory plate can be installed for the purpose of mounting optional auxiliary
boards. The accessory plate mounts onto the main chassis, as shown in
Figure 18.