Chapter 1: Installation overview
20
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
<
,
:
-
3.
Z-Port 2
Optional
Serial board ZP3AB-NET-RS485 for connecting to
a Ziton ZP-NET peer-to-peer network comprising
several ZP3 panels, Maestro graphics computers,
and global display panels.
4.
Serial control
board
Optional
Serial board ZP3AB-SCB-D for connecting to one
or more remote display panels, remote control
panels with inputs and outputs (sounders, control
outputs, etc), and remote mimic indicator panels.
The ZP3AB-RS232 Serial Communications Board (see Figure 13) is used to
connect a ZP3 panel to an external device, such as a desktop printer, a graphics
display system, a building management system, modem, or a paging system.
The hardware protocol is a RS-232, being a screened five-wire connection. The
RS-232 board is defined in the menus as Port1a, and different software protocols
can be selected to match the connected PC application. Communication
parameters can be set in the Setup menu.
5
4
!
6
+
4
3
;
0
:
"
4
"
:
-
;
6
0
+
1
1
14
25
13
5
6
9
9-pin D
connector
25-pin D
connector
Z-Port 1a
ZP3AB-RS232 board
Cable connections
(Ziton RS232 Type A Cable)
ZP3 Panel
(9-pin)
Computer
(9-pin) (25-pin)
2
3
4
5
6
7
8
3
2
8
5
7
2
3
5
7
4
RX
TX
DTR
GND
DSR
RTS
CTS
TX
RX
CTS
GND
RTS
9-pin D
connector
1
5
6
9
RS-232 is officially specified as a maximum cable length of 10 metres. However,
if slower baud rates are used, then it is possible to operate it at up to 50 metres.
Cable must be screened, with at least five conductors, and must be made up as
shown in Figure 13.