Appendix B: ZP3 system maintenance
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
145
$
1
(
>
>
!
>
#
ZP740ST
Analogue interface for
high sensitive smoke
detector (stratos)
233
197-226 (213)
165-194 (180)
165-194 (180)
ZLS1APIC
Analogue interface for
high sensitive smoke
detector (stratos)
233
197-226 (213)
165-194 (180)
165-194 (180)
ZP755
Loop sounder (all
variants)
241
197-226 (213)
133-162 (152)
228-255 (245)
ZP750-2
Line relay
242
197-226 (213)
133-162 (152)
197-226 (213)
A50E
Line relay
242
197-226 (213)
133-162 (152)
197-226 (213)
A51E
High voltage line relay
242
197-226 (213)
133-162 (152)
197-226 (213)
ZP752-2
Dual line sounder unit
245
197-226 (213)
133-162 (152)
102-131 (118)
ZP753-2
Addressable LED
indicator
246
197-226 (213)
133-162 (152)
070-100 (084)
ZP754*-2
Addressable line sounder 247
197-226 (213)
133-162 (152)
039-068 (054)
ZP755
Loop sounder (ZP754
mode)
247
197-226 (213)
133-162 (152)
039-068 (054)
ZP5-IF8-52
Eight-way interface fire
non-fire/auxiliary board
252
197-226 (213)
102-131 (118)
197-226 (213)
ZP740-2-52
Analogue interface non-
fire/auxiliary
252
197-226 (213)
102-131 (118)
197-226 (213)
ZP5-IF8-53
Eight-way interface fire
non-alarm/control board
253
197-226 (213)
102-131 (118)
165-194 (180)
ZP740-2-53
Analogue interface non-
alarm/control
253
197-226 (213)
102-131 (118)
165-194 (180)
ZP5-IF8-54
Eight-way interface fire
non-alarm/control board
254
197-226 (213)
102-131 (118)
133-162 (152)
ZP740-2-54
Analogue interface non-
alarm/control
254
197-226 (213)
102-131 (118)
133-162 (152)
ZP5-IF8-62
Eight-way interface fire
security latching board
262
197-226 (213)
070-100 (084)
197-226 (213)
ZP740-2-62
Analogue interface
security latching
262
197-226 (213)
070-100 (084)
197-226 (213)
ZP5-IF8-64
Eight-way interface fire
security non-latching
board
264
197-226 (213)
070-100 (084)
133-162 (152)
ZP740-2-64
Analogue interface
security non-latching
264
197-226 (213)
070-100 (084)
133-162 (152)
ZX832-2
Analogue duet sensor
(paradigm) optical/heat
416
133-162 (152)
228-255 (245)
070-100 (084)
ZR420
Radio heat detector
423
133-162 (152)
197-226 (213)
165-194 (180)
ZR485
Radio call-point
424
133-162 (152)
197-226 (213)
133-162 (152)
ZR430
Radio optic detector
425
133-162 (152)
197-226 (213)
102-131 (118)
Radio aux.
Radio auxiliary interface
426
133-162 (152)
197-226 (213)