Appendix B: ZP3 system maintenance
152
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
8
*
8
1
(
>
>
7
15. LED 37
Internal supply 24 VDC
-
Green: On = supply on, Off =
supply faulty
16. LED 15
Internal supply for CPU
(5 VDC)
-
Green: On = supply on, Off =
supply faulty
17. LED 14
Internal supply for logic
(5 VDC)
-
Green: On = supply on, Off =
supply faulty
18. LED 8
Internal supply for
RS-232 (12 VDC
í
ve)
-
Green: On = supply on, Off =
supply faulty
19. LED 7
Internal supply for
RS-232 (12 VDC +ve)
-
Green: On = supply on, Off =
supply faulty
20. LED 2
Internal supply for
ZP3AB-SCB-D control
bus driver
-
Green: On = supply on, Off =
supply faulty
21. LED 4
Mains 230 VAC supply
-
Green: On = supply on, Off =
supply faulty
22. Fuse FM Mains fuse
F5AL250VAC
BS1362
The backup batteries may need to be replaced for a number of reasons, for
example, end-of-life, insufficient capacity, etc.
• The backup batteries, although only 24 VDC, carry enough charge to be
dangerous.
• When connecting batteries, or when working in the vicinity of the battery
terminals, take care not to accidentally cause a short circuit. In particular
metallic tools or metallic watchstraps can also inflict
Ë
Î
D
Î
ó
Î
burns to the user
as well as cause a short circuit.
The backup batteries contain substances that are potentially hazardous
to your health and to the environment.
1. Disconnect the connections from the positive and negative terminals on the
backup batteries.
2. Loosen and remove the wing nut from the batteries securing bracket (see
Figure 68 on page 153).
3. Remove the bracket securing the backup batteries to the chassis.
4. Remove the backup batteries.
5. Install new backup batteries as described under “Backup batteries” on page
46.