Chapter 1: Installation overview
4
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
3
9
-
-
Output voltage (mains on)
24 VDC nominal
See note 1
Output voltage (mains off)
18.0 to 27.6 VDC
See note 1
Battery charging voltage
27.6 VDC
at 20
q
C temperature
compensated
Maximum ripple (at full load)
500 mV peak
2
Total continuous
2.6 A at 21 VDC
See note 2
Total continuous
3.0 A at 24 VDC
See note 2
Total peak
5.5 A at 24 VDC
See note 2
Panel operation (quiescent)
0.4 A
See note 3
Panel operation (fire)
0.6 A
See note 3
Battery charging (JP6 IN,
default)
1.4 A
Battery charging (JP6 OUT)
1.0 A
Available to user (continuous
non fire alarm)
1.2 A
See note 4
Available to user (continuous in
fire alarm)
2.5 A
See note 5
:
-
-
High voltage alarm
28.5 VDC
First battery low-voltage
notification: battery low warning
local
22.3 VDC
Second battery low-voltage
notification: low/no battery local
21.0 VDC
;
Type
12 V (2X)
Sealed lead-acid as per “Power
supply and battery calculations”
on page 56
Make and model
—
Kung Long WP26-12
BS129N
Battery SLA type
26 A/H
Maximum size that can be
fitted into a type-A cabinet
Lithium battery CR2325
6 VDC
Time and date retention
+
-
8
1
Panel (quiescent at 24 VDC)
450 mA
Load of panel only, excluding
any external devices
Panel (alarm at 24 VDC)
500 mA
Load of panel only, excluding
any external devices
Per Loop (quiescent at 24
VDC)
150 mA
Fully loaded loop, with 127 ZP
devices, not in alarm