Chapter 1: Installation overview
18
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
RS-232 is officially specified as having a maximum cable length of 10 metres,
which is more than adequate for ZP3/PC configuration functions. The connecting
cable must be screened, and must be made-up as per Figure 10. Alternatively, a
standard null modem cable can be used.
The RS-232 built-in serial port (Zport1) must be configured in the software, and
must be set to match the communications parameters of the PC and program
being used.
Access the communications parameters menu using the following menu path:
Setup > System Configuration > Peripheral Comms > Comms Parameters
The following screen is displayed.
5
!
+
To change a setting, move the bracket to the selected item, and press Enter.
The parameters are dependent on the program used. For Planner, set the
parameters as follows.
&
-
$
!
6
0
+
Z-PORT
Enter Z-port number 1
Protocol
Enter the required protocol as follows:
0 = disable the port
11 = for use with Ziton Planner
18 = ZCP2-3 protocol
Setup
Enter the following setup data:
Baud rate = 38400
Data bits = 8
Parity = None
Stop bits = 1