Appendix B: ZP3 system maintenance
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
147
The device status reading is sometimes also referred to simply as the analogue
reading. It is a precise indicator of how strongly the device is sensing the
environmental factors (e.g. heat or smoke) it is designed to detect. For some
devices the analogue reading may indicate some other measure such as the
status of a switch.
The panel interprets the reading according to the device type. The panel uses
sophisticated algorithms based on these readings and their change over time to
determine the true conditions in the area covered by the device. Viewing a
snapshot of the analogue readings cannot provide information with the same
degree of accuracy; nevertheless values can be interpreted, as in the following
tables, in order to help assess the status of a device.
The resting values of the analogues when devices are in normal conditions are
provided in Table 53. The resting value is referred to as the idle value and can
take on any values in the ranges given below, usually this is near the midpoint of
the range.
&
"
#
B
$
C
!
#
$
5
ZP710-2
20–108
20–108
20–108
20–108
ZP720-2
25–123
25–143
25–186
25–186
ZP725-2
25–123
25–151
25–174
25–194
ZP730-2
20–108
20–108
20–108
20–108
ZP732-2 optic
20–108
20–108
20–108
20–108
ZP732-2 heat
25–163
25–163
25–179
25–179
ZP720-3
25–123
25–163
25–179
25–179
ZP740-2
59–137
59–137
59–137
59–137
ZP745
59–137
59–137
59–137
59–137
ZP770-2
59–137
59–137
59–137
59–137
ZP740ST
39–104
39–104
39–104
39–104
ZP755
40–110
40–110
40–110
40–110
ZP750-2
59–140
59–140
59–140
59–140
ZP752-2
40–140
40–140
40–140
40–140
ZP753-2
40–110
40–110
40–110
40–110
ZP754*-2
40–110
40–110
40–110
40–110
ZP5-IF8
59–137
59–137
59–137
59–137
ZX832-2 optic
20–100
20–100
20–100
20–100
ZX832–2 heat
25–164
25–164
25–179
25–179
ZR420
85
85
85
85