Chapter 4: Software programming
78
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
outputs can be assigned a range of attributes to create the required functions.
Each input can be linked to several outputs, with different attributes for each.
The menu path is: Setup > I-O Mapping. The available options are described in
Table 18.
Ê
³
Õ
´
©
Ó
Ä
¬
Ò
Â
Ç
Æ
³
¶
¶
¥
°
¦
®
¶
µ
¥
®
°
·
Ç
¶
µ
¥
®
°
×
©
·
»
¨
¥
¶
µ
¥
®
°
I/O Map View
View I/O mapping. Enter the output address to view and press Enter.
The display shows the output address, its attributes, and its
identification message. It also shows the total number of outputs
mapped. Using the scroll feature displays the linked inputs and their
attributes.
I/O Map Edit
Add new I/O map entries or edit existing entries. Proceed as follows:
Enter the output address, and press Enter. The output is shown, with
default attributes that can be changed. Use F2 to create (or edit) an
output identification message. Choose Done when complete.
The display switches to the input screen, and allows inputs to be
assigned. Each input address entered is presented with default
attributes that can be changed. Select Done when complete, and the
next input is presented.
Press Esc to select the next output address after all inputs are assigned.
Press Home to exit the menu, and save the I/O mapping once complete.
Note: The addresses of Control Nodes can be mapped as inputs only.
The Control nodes are addressed as group 26; address range 0 to 255.
I/O Map Clear
Clear (delete) all I/O mapping entries. A level 3 code is required before
the I/O map can be deleted.
Global Reactivate
This option is used to globally set the reactivation rules for outputs that
have been defined as silencing. It also defines their behaviour after they
have been silenced, when a second alarm is received. Two options are
available:
Own I/Ps. This means that if the output is silenced, it only reactivates if
a second alarm is received from an input that is mapped to it.
Any Fire. This means that if the output is silenced, it reactivates from
any second alarm, regardless of the source.
The View menu lets the operator view the configurations of individual points
connected to the Z-loops.
The menu path is: Setup > Points > Individual Settings > View. The available
options are described in Table 19.