Appendix B: ZP3 system maintenance
140
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
Remote alarm
Display the enabled/disabled status of the remote alarm relay (fire
brigade) switched outputs. Both the alarm and fault outputs can be
viewed in this menu.
&
"
5
"
.
1
"
<
(
0
Menu path
Maintenance > Edit or View Disabled (Points, Zones)
Purpose
This menu lets you temporarily disable an address in half hour intervals.
This allows multiple zones and line input devices to be disabled but not
panel or panel bus outputs. After the period expires, the address
enables again automatically. The menu allows the user to select Auto
Enable, after a disablement period configurable from 30 minutes to 12
hours.
Points
To auto enable any point select Edit Disabled from the Maintenance
menu. Select the point to be auto enabled and select Auto, using the
arrows to scroll up or down to set the required time period. Use the
scroll feature to display the next or previous point to be disabled. Use
the Enter key to confirm the selection.
Zones
To auto enable zones select Edit Disabled from the Maintenance menu.
Select the zones to be auto enabled and select Auto, using the arrows
to scroll up or down to set the required time period. Use the Enter key to
confirm the selection.
Note: The disabled status can be overridden by:
•
A local enable event from the local panel
•
A remote enable event from a remote panel via the peer to peer
network
•
A change over from day to night mode may extend the disabled
period to coincide with the Disable by Night setting.
In the case of dual-sensor detectors, both smoke and heat elements are
disabled.
&
"
5
:
"
Menu path
Maintenance > Enable All
Purpose
This menu provides a quick method to enable points and outputs or
both. The menu options available are: Enable all…
Points
Enable all system Z-loop devices. This includes sensors, call points,
devices, zones, and loop or base sounders.
Outputs
Enable all panel outputs. This includes all extinguishing control units,
panel sounder outputs, and the remote manned centre output.
Points and Outputs
Enable all Z-loop devices and panel outputs, i.e. this is the same as
selecting both options above.
&
"
5
=
>
(
1
(
Menu path
Maintenance > Reports to Display
Purpose
This menu provides a selection of reports to view on the display. Report
messages can be manually or automatically scrolled. The reports that
can be viewed are listed below with a brief description of each report.