Chapter 4: Software programming
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
73
¤
¥
¦
§
¨
©
«
É
¬
¾
¨
®
¦
¨
³
¯
¯
¥
°
¦
¯
©
°
§
©
Ø
³
¯
¶
´
©
·
1. Access the following menu: Setup > System Configuration > Peripheral
Comms > Comms Parameters.
2. Select the required port to configure as follows:
Press the Up or Down Arrow button to move the selection brackets to Z-Port.
Press the Left or Right Arrow button to select the required Z-port (i.e. 1 or 2).
3. Select the required communications protocol as follows:
Press the Up or Down Arrow button to move the selection brackets to
Protocol.
Press Enter. A list of available protocols is displayed.
Select the required protocol using the Up or Down Arrows, and then press
Enter.
4. Select the required communications protocol parameters as follows:
Press the Up or Down Arrows to select Setup.
Press Enter. A list of available parameters is presented.
Press the Left or Right Arrows to select each parameter, and then press
Enter.
Press the Up or Down Arrows to select the required value, and then press
Enter.
Select Done after setting the required parameters, and then press Enter.
5. When you have finished, press Esc to save the programming.