Chapter 1: Installation overview
ZP3 Fire Control Panel Installation, Commissioning, and Maintenance Manual
23
5
$
!
+
To change a setting, move the bracket to the selected item, and then press
Enter.
The parameters are dependent on the program used. The following options are
available.
&
-
>
!
6
0
"
+
Z-PORT
Enter Z-port number 2
Protocol
Enter the required protocol as follows:
0 = Used for stand-alone panels (not networked)
9 = Peer-to-Peer networking
10 = Peer-to-Peer V2
17 = Peer-to-Peer V3
Setup
Enter the following setup data:
Baud rate = 19200
Data bits = 8
Parity = Even
Stop bits = 1
The ZP3AB-SCB-D Serial Control Bus Driver Board is used to connect a number
of remote display units (RDUs) and remote control units (RCUs) to a ZP3 fire
panel. The hardware protocol is a multidrop RS-485 screened, two-wire
connection. The wiring is connected from the ZP3AB-SCB-D board in the ZP3
panel to the SCB connections in the RDU and RCU panels. The wiring must be
terminated at the ZP3 panel by connecting the jumpers as shown in Figure 17.
All other panels must not be terminated, i.e. their jumpers must be removed.