User Constant Settings and Functions
5.6.1 External Regenerative Resistors
5 -82
J
J
Connecting Regenerative Resistors
The method for connecting regenerative resistors is shown below.
Servopacks with Capacities of 400 W or Less
Connect an external regenerative resistor between the Servopack’s B1 and B2 terminals.
Servopack
B1
B2
Regenerative resistor
*
The user must provide the regenerative resistor.
Servopacks with Capacities of 0.5 to 5.0 kW
Disconnect the wiring between the Servopack’s B2 and B3 terminals and connect an external
regenerative resistor between the B1 and B2 terminals.
Servopack
B1
B2
Regenerative resistor
Be sure to take out the lead wire
between the B2 and B3 terminals.
B3
*
The user must provide the regenerative resistor.
Servopacks with Capacities of 6.0 kW or More
Servopacks with capacities of 6.0 kW or more do not have regenerative resistors built in. A re-
generative resistor must be connectedexternally. Thefollowing RegenerativeResistor Unitsare
available for this purpose.
Servopack
Applicable
Regenerative
Resistor Unit
Resistance
(W
)
Specifications
SGDH-60AE
JUSP-RA04
6.25
25
W
(220 W)
´
4 resistors in parallel
SGDH-75AE to
-1EAE
JUSP-RA05
3.13
25
W
(220 W)
´
8 resistors in parallel
SGDH-60DE,
-75DE
JUSP-RA18
18
18
W
(220 W)
´
4 resistors
in serial-parallel
SGDH-1ADE,
1EDE
JUSP-RA19
14.25
28.5
W
(220 W)
´
8 resistors
in serial-parallel
5