7.2 Applied Operation
7 -21
Using the Panel Operator
1.
Press the MODE/SET Key to select the “Displaying alarm traceback data (Fn000)” in the
auxiliary function mode.
Alarm Traceback
Display
2.
Press the DATA/SHIFT for a minimum of one second to display the alarm traceback data.
3.
Press the Up Cursor Key or Down Cursor Key to scroll the alarm sequence numbers up or
down and display information on previous alarms.
The higher the left-hand digit (alarm sequence number), the older the alarm data.
For descriptions of each alarm code, refer to
Section 8.2 Troubleshooting.
The following are Operator-related alarms which are not recorded in the traceback data.
Digital Operator transmission error 1
Digital Operator transmission error 2
The display will be as shown below while no alarm is detected.
Alarm traceback data will not be updated when the same alarm occurs repetitively.
7
SGDH
-
MODE/SET
DATA/
CHARGE
POWER
SERVOPACK
200V
YASKAWA