5.5 Forming a Protective Sequence
5 -75
Signals output when Servomotor operation is detected:
D
/TGON
D
Status Indication Mode
D
Monitor Mode Un006
5.5.6 Using the Servo Ready Output Signal
The basic use and wiring procedures for the Servo Ready (/S-RDY) output signal (photocoupler
output signal) are described below.
Servo Ready means there are no Servo alarms and the main circuit power supply is turned ON.
An added condition with absolute encoder specifications is that the SEN signal is at high level
and absolute data was output to the host controller.
CN1-29
CN1-30
/S-RDY+
/S-RDY--
+24 V
0 V
Photocoupler output
(per output)
Maximum operating voltage:
30 VDC
Maximum output current:
50 mA DC
Servopack
I/O power supply
Output
®
/S-RDY CN1-29
Servo Ready Output Signal
Speed/Torque
Control,
Position Control
This signal indicates the Servopack received the Servo ON signal and completed all prepara-
tions.
ON:
Closed or low level
Servo is ready.
OFF:
Open or high level
Servo is not ready.
The following user constant setting is used to change the CN1 connector terminal that outputs
the /S-RDY signal.
Pn50E
Output Signal Selections 1
Factory
Setting:
3211
Speed/Torque
Control,
Position Control
The user constant isfactory set so the /V-CMPsignal isoutput between CN1-29 and 30. See
5.3.4
Output Circuit Signal Allocation
for more details on user constant Pn50E.