7.2 Applied Operation
7 -53
Using the Panel Operator
1.
Press the MODE/SET Key to select the auxiliary function mode.
2.
Press the Up or Down Cursor Key to select the user constant Fn014.
3.
Press the DATA/SHIFT Key for a minimum of one second, and the display will be as shown
below.
4.
Pressthe MODE/SETKey, andthe displaywill beasshownbelow. Theoption unitdetection
results will be cleared.
Flashing for
one second
Flashing during
initialization
End
5.
Press the DATA/SHIFT Key to return to the auxiliary function mode display.
This completes the clear of the option unit detection results.