Using the Digital Operator
7.2.10 Manual Zero Adjustment and Gain Adjustment of Analog Monitor Output
7 -42
J
J
Manual Zero Adjustment of Analog Monitor Output
Follow the procedure below to execute the manual zero adjustment of analog monitor output.
Using the Hand-held Digital Operator
1.
Press the DSPL/SET Key to select the auxiliary function mode.
2.
Select the user constant Fn00C.
Press the Left or Right Cursor Key to select the digit.
Press the Up or Down Cursor Key to change the value.
3.
Press the DATA/ENTER Key, and the display will be as shown below.
4.
Press the DSPL/SET Key, and the monitor output for the two channels will be displayed al-
ternately as shown below.
DSPL/SET Key
Displayed
alternately
Data Display
5.
Press the Left or Right Cursor Key to display the analog monitor output data. Pressing the
Left or Right Cursor Key again will return to the display shown in the above step
LEERER MERKERor LEERER MERKER
Displayed
alternately
Left Cursor Key
(Right Cursor Key)
Data Display
6.
Press the Up or Down Cursor Key to perform zero adjustment of the analog monitor output.
Data Setting Change
7.
When zero adjustment has been completed for the two channels, press the DATA/ENTER
Key to return to the auxiliary function mode display.
This completes the manual zero adjustment of the analog monitor output.