User Constant Settings and Functions
5.3.4 Output Circuit Signal Allocation
5 -56
Output Signal
User Constant
Description
Number
Setting
Positioning
Completed
Pn50E.0
0
Disabled (Not used for the output signal on the left.)
Completed
(/COIN)
1
Outputs the signal on the left from the SO1 (CN1-25 and 26) output terminal.
(/COIN)
2
Outputs the signal on the left from the SO2 (CN1-27 and 28) output terminal.
3
Outputs the signal on the left from the SO3 (CN1-29 and 30) output terminal.
Speed
Coincidence
Detection
(/V-CMP)
Pn50E.1
0 to 3
Same as above
Rotation
Detection
(/TGON)
Pn50E.2
0 to 3
Same as above
Servo Ready
(/S-RDY)
Pn50E.3
0 to 3
Same as above
Torque Limit
Detection
(/CLT)
Pn50F.0
0 to 3
Same as above
Speed Limit
Detection
(/VLT)
Pn50F.1
0 to 3
Same as above
Brake Interlock
(/BK)
Pn50F.2
0 to 3
Same as above
Warning
(/WARN)
Pn50F.3
0 to 3
Same as above
Near
(/NEAR)
Pn510.0
0 to 3
Same as above.
Not used.
--
--
--
Note
“Same as above” means output signals are disabled or allocated to output terminals SO1 to SO3 through user
constant settings 0 to 3.
Signals are output with OR logic when multiple signals are allocated to the same output circuit. Signals that
are not detected are invalid. For example, the positioning completed signal /COIN is invalid in Speed Control
Mode.
The following user constant can be used to reverse the signals output on output terminals SO1
to SO3.
Pn512
Output Signal Reversal Settings
Factory
Setting:
0000
Speed/Torque
Control,
Position Control
The settings specify which of the connector CN1 output signals are to be reversed.
5
INFO