User Constant Settings and Functions
5.7.4 Absolute Encoder Setup
5 -96
4.
Pressing the Up Cursor Key will change the display as shown below. Continue pressing the
Up Cursor Key until “PGCL5” is displayed. If an erroneous key entry is made, “nO_OP”
will flash for one second and the display will return to the auxiliary function mode. In that
case, go back to step 3 above and perform the operation again.
Up Cursor Key
When a Mistaken Key Entry is Made
Flashes for one second.
Returns to auxiliary function mode.
Up Cursor Key
5.
When “PGCL5” isdisplayed, pressthe DSPL/SET Key. The display will change asfollows,
and the absolute encoder’s multi-turn data will be cleared.
Flashes for
1 second.
6.
Press the DATA/ENTER Key to return to the auxiliary function mode.
This completes the absolute encoder’s setup operation. Turn the power OFF and then back ON
again.
J
J
Setup Using the Built-in Panel Operator
1.
Press the DSPL/SET Key to select the auxiliary function mode.
2.
Press the Up or Down Cursor Key to select the user constant Fn008.
3.
Press the DATA/SHIFT Key for at least one second. The following display will appear.
4.
Pressing the Up Cursor Key will change the display as shown below. Continue pressing the
Up Cursor Key until “PGCL5” is displayed. If an erroneous key entry is made, “nO_OP”
will flash for one second and the display will return to the auxiliary function mode. In that
case, go back to step 3 above and perform the operation again.
Up Cursor Key
Up Cursor Key
When a Mistaken Key Entry is Made
Flashes for one second.
Returns to auxiliary function mode.
5