5.4 Setting Stop Functions
5 -63
Pn000.1 Setting
Control Mode
A
Zero Clamp Control Mode
This mode allows the zero clamp
function to be set when the Servo-
motor stops.
S
The speed reference is input from
V-REF (CN1-5).
S
/P-CON (/ZCLAMP)(CN1-41) is
used to turn the zero clamp func-
tion ON and OFF.
Zero clamp
V-REF
CN1-5
CN1-41
/P-CON
Servopack
(/ZCLAMP)
Speed reference
CN1-41 is
open (OFF).
Turns the
zero clamp
function
OFF.
Zero clamp is performed when the fol-
lowing two conditions are satisfied:
Condition 1: /P-CON (/ZCLAMP) is
ON.
CN1-41 is 0
V (ON).
Turns the
zero clamp
function ON.
ON.
Condition 2: Speed reference is below
the setting at Pn501.
J
J
Setting
Use the following user constant to set the motor speed level at which zero clamp is performed.
Pn501
Zero Clamp Level
Unit:
r/min
Setting
Range:
0 to 10000
Factory
Setting:
10
Speed Control
Set the motor speed at which zero clamp is performed if zero clamp speed control is selected.
Even if this value is set higher than the maximum speed of the Servomotor, the maximum speed
will be used.
Zero Clamp Conditions
Zero clamp is performed when all the following conditions are satisfied:
D
Zero clamp speed control is selected (user constant Pn000.1 is set to A).
D
/P-CON (/ZCLAMP)(CN1-41) is ON (0 V).
D
Speed reference drops below the setting of Pn501.
V-REF speed reference
Speed
Preset value for zero clamping
/P-CON (/ZCLAMP) input
Zero clamp is performed.
Open (OFF)
Closed
(ON)
Time
5