Meter Type
: Indicates the type of register connected to the SmartPoint. Valid register
types are Sensus TouchCoupler, Sensus 3 Wire, Neptune Proread E-Coder, AMCO
Scancoder, Elster InVISION, and Badger ADE. There is also an option to AutoDetect
the type of register. Alternatively, this value can be set to Not Used if no register is to be
connected to the specific port on the SmartPoint.
•
Units
: Indicates the meter's units of measure. Valid values are Gallons, Liters, Cubic
Feet, and Cubic Meters.
•
Resolution
: Will be one of the following valid values: 0.1x, 1x, 10x, 100x, 1000x, 0.01x,
and 10000x.
•
Leak Detection Threshold
: This value is used to determine a leak condition. Will be one
of the following valid values: Disabled, 1 Count, 2 Counts, or 10 Counts.
•
Leak Detection Consecutive Reads
: If the meter reports a reading that exceeds the
threshold for this number of consecutive readings, then a leak condition will be flagged
by the SmartPoint. Will be one of the following values: 24, 36, 48, and 72.
•
Backflow Threshold
: This value is used to determine a leak condition. Will be one of the
following valid values: Disabled, 1 Count, 2 Counts, 5 Counts, 10 Counts or 100 Counts.
3 Polling Devices | 36