Graphical Digital Panel Meter WPMZ-3 INSTRUCTION MANUAL
43
IM-0883-01
LinearizePoint
*This setting item can be set only when “InputCorrect” is “Linearize”.
Set the correction value for 16 points of the linearize function.
After the second point, if both the pre-correction and post-correction set values are set to 0, it is judged to be a
termination, and the subsequent correction points are invalidated.
ex)
In the case of a sensor whose output is dull when the load is large.
(Display value is 0 to 8000 corresponding to 0 to 10 V input)
1stInput :
0
1stOutput:
0
2ndInput :
5000
2ndOutput:
5000
3rdInput :
5800
3rdOutput:
6000
4thInput :
6500
4thOutput:
7000
5thInput :
7000
5thOutput:
8000
6thInput :
0 (Disabled)
6thOutput:
0 (Disabled)
(7 to 16 points are disabled)
Operation:[MENU]
⇒
[Input]
⇒
[StrainInputA][StrainInputB][ProcessInputA][ProcessInputB]
⇒
[LinearizePoint]
Setting value:
1stInput : ±99999 (Default is 0)
1stOutput: ±99999 (Default is 0)
2ndInput: ±99999 (Default is 1000)
2ndOutput: ±99999 (Default is 1000)
・
・
・
15thInput: ±99999 (Default is 14000)
15thOutput: ±99999 (Default is 14000)
16thInput: ±99999 (Default is 15000)
16thOutput: ±99999 (Default is 15000)
DispShift
Set offset of display value.
Operation:[MENU]
⇒
[Input]
⇒
[StrainInputA][StrainInputB][ProcessInputA][ProcessInputB]
⇒
[DispShift]
Setting value:
±99999(Default is 0)
TrackingZero
Tracking zero is a function that automatically corrects minute offset of display value over time. The judgment is
made at each setting time, and if the display value is within 0 ± “ActiveArea”, offset correction is performed and
the display value becomes 0.
While the tracking zero function is in operation, the "TZ" mark will light on the upper right of the display value
of the measurement screen.
* The tracking zero function operates only when the digital zero function operates, and it works automatically
when the function is enabled and when the function of the digital zero function starts.
Sensor load
Actual sensor output
Ideal sensor output
8.75V(Display value is 7000)
Output graph of sensor which output becomes nonlinear at high load
10V(Display value is 8000)
6.25V(Display value is 5000)
Linear up to display value 5000