![WATANABE WPMZ-3 Series Скачать руководство пользователя страница 40](http://html2.mh-extra.com/html/watanabe/wpmz-3-series/wpmz-3-series_instruction-manual_3500829040.webp)
Graphical Digital Panel Meter WPMZ-3 INSTRUCTION MANUAL
39
IM-0883-01
OnConditions
Select output ON condition.
Setting value of [OnConditions] changes by setting value of [CompareMode].
*If setting value of [CompareMode] is “Diffjudge”, [OnConditions] is invisible.
Operation: [MENU]
⇒
[Output]
⇒
[CompareAL1], [CompareAL2], [CompareAL3], [CompareAL4]
⇒
[OnConditions]
[CompareMode] is “Leveljudge”
Setting value: Excess(Default), LessThan
[CompareMode] is “Zonejudge”
Setting value: InTheZone(Default), OutsideTheZone
Threshold
Set threshold for comparison output.
Setting value of [Threshold] changes by setting value of [CompareMode].
Operation:[MENU]
⇒
[Output]
⇒
[CompareAL1], [CompareAL2], [CompareAL3], [CompareAL4]
⇒
[Threshold]
[CompareMode] is “Leveljudge”
Setting value: Threshold
±99999 (Default is10000)
Hysteresis 0
~
99999(Default is 0)
[CompareMode] is “Zonejudge”
Setting value:
ZoneLowerLimit
±99999 (Default is 0)
ZoneUpperLimit
±99999 (Default is 10000)
Hysteresis 0
~
99999(Default is 0) *Same hysteresis is applied in ZoneLowerLimit and
ZoneUpperLimit.
[CompareMode] is “Diffjudge”
Comparison output turns ON when
(
MAX - MIN
)
> ChangeAmount (See below)
Setting value: ChangeAmount
0
~
99999 (Default is 10000)
DetectionInterval 0.00
~
99.99[sec] (Default is 1.00)
*If “DetectionInterval” is 0.00, “Diffjudge” is disabled.