Graphical Digital Panel Meter WPMZ-3 INSTRUCTION MANUAL
36
IM-0883-01
PatternSelect
You can store and set up 8 patterns (8 kinds) of various settings such as input and output with this unit, you can
select the pattern to save the setting in "PatternSelect".
The pattern number being set is displayed as "P5" on the upper right of the setting screen as shown below.
Operation:[MENU]
⇒
[Output]
⇒
[AnalogOutput]
⇒
[PatternSelect]
Setting value:Pattern1, Pattern 2,
・・・・・
Pattern 8
* At the time of opening the menu, the setting pattern is the value selected as operating on the measurement
screen.
* Since the setting pattern is common in each setting, "PatternSelect" such as input setting is also changed when
"PatternSelect" is changed by "AnalogOutput”.
OutputRange
Select output range of analog output.
*Be careful to connect output terminals. There are 2 terminals that one of it is for voltage output, and another is
for current output. (For wiring, please confirm "CONNECTING TERMINALS”.)
Operation:[MENU]
⇒
[Output]
⇒
[AnalogOutput]
⇒
[OutputRange]
Setting value: 0-10V (Default) (Load resistance of 2 kΩ or more)
±10V
(Load resistance of 2 kΩ or more)
1-5V
(Load resistance of 2 kΩ or more)
0-20mA (Load resistance of 550 Ω or less)
4-20mA (Load resistance of 550 Ω or less)
OutputDispValue
Select reference source of analog output.
*In 1ch products, [Bch] and [Calc] are invisible.
Operation:[MENU]
⇒
[Output]
⇒
[AnalogOutput]
⇒
[OutputDispValue]
Setting value: None(Default), Ach, Bch, Calc
OutputScale
Select the display value that corresponding to output scale 0% and 100%.
Analog output is referred display value.
(ex: [“OutputRange” is 4-20mA and “0%DispValue” is 2000 and “100%DispValue” is 8000]
4mA is outputted when display value is 2000, and 20mA is outputted when display value is 8000)
Operation:[MENU]
⇒
[Output]
⇒
[AnalogOutput]
⇒
[OutputScale]
Setting value: 0% DispValue: ±99999 (Default is 0)
100% DispValue: ±99999 (Default is 10000)