Graphical Digital Panel Meter WPMZ-3 INSTRUCTION MANUAL
120
IM-0883-01
1st Layer
2nd Layer
3rd Layer
(setting items)
4th Layer (setting values)
Remarks
Initial values
Settable values
2. Output
CompareAL1
CompareAL2
CompareAL3
CompareAL4
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
OutputDispValue
None
None/Ach/Bch/Calc
ActCondition
Always
Always/ExceptNearZero/OnStable
/ OnStableExceptNearZero/OnHold
Select a condition of comparion.
ComparedMode
LevelJudge
LevelJudge/ZoneJudge/DiffJudge
OnConditions
Excess
Excess/LessThan
Only LevelJudge.
InTheZone
InTheZone/OutsideTheZone
Only ZoneJudge.
Threshold
10000
0
Threshold:
±99999
Hysteresis:
0
~
99999
Only LevelJudge.
0
10000
0
ZoneLowerLimit:
±99999
ZoneUpperLimit:
±99999
Hysteresis:
0
~
99999
Only ZoneJudge.
10000
1.00
ChangeAmount:
0
~
99999
DetectionInterval:
0.00
~
99.99[sec]
OnDelay
None
None/20ms/50ms/100ms/200ms/500ms
1s/5s/10s/20s
Compare ON/OFF after ActCondition is
kept certain time set here.
OffDelay
None
OutputMode
Normal
Normal/Latch/OneShot5ms/10ms/20ms
/50ms/0.1s/0.2s/0.5s/1s/2s
Select an output mode.
OutputLogic
Negative
Positive/Negative
Select an output logic.
OnBgColors
Black
Black/Red/Yellow/Green
Select a background color when
alarming.
AnalogOutput
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
OutputRange
0-10V
0-10V/±10V/1-5V/0-20mA/4-20mA
Select a type of output range.
OutputDispValue
None
None/Ach/Bch/Calc
Select a ch referenced for analog output.
OutputScale
0
10000
0%:
±99999
100%:
±99999
Scaling of analog output.
Set 0% and 100% value.
BCD Output
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
OutputDispValue
None
None/Ach/Bch/Calc
Select a ch referenced for BCD output.
DataSignalLogic
Negative
Positive/Negative
Select an output mode.
SyncSignalLogic
Negative
Positive/Negative
Select an output mode.
ModbusCom
SlaveAddress
1
1
~
31
Set ID of the product.
Baudrate
19200bps
9600bps/19200bps/38400bps
Select a baudrate.
Parity
Even
None/Even/Odd
Select a type of parity bit.
RS-232C Com
Protocol
Modbus-RTU
ModbusRTU/OriginalCommand/OriginalO
utput
Select a protocol.
Baudrate
19200bps
9600bps/19200bps/38400bps
Select a baudrate.
Parity
Even
None/Even/Odd
Select a type of parity bit.
DataLength
7bit
7bit/8bit
Enable when Protocol is
OriginalCommand or OriginalOutput.
Stopbit
1bit
1bit/2bit
Delimiter
CR LF
CR / CR LF
3.Display
DispSelect
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
MeasureSelect
1ch product
Ach, Ach + Comp
Level, Trend
2ch product
Ach + Bch,
Level, Trend
Ach/Bch/Calc/Ach+Comp/Bch+Comp
/Calc+Comp/Ach+Bch/Calc+A+B
*Bch and Calc is enable in 2ch product.
LevelSelect
Ach/Bch/Calc/Ach+Bch
*Bch and Calc is enable in 2ch product.
TrendSelect
LevelDisp
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
Ach Scale
0
10000
LowerLimit:
±99999
UpperLimit:
±99999
Set scale of level screen.
Bch Scale
CalcScale
AL Select
AL1
~
AL4:ON
AL1/AL2/AL3/AL4
TrendDisp
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
Ach Scale
0
10000
LowerLimit:
±99999
UpperLimit:
±99999
Set scale of level screen.
Bch Scale
CalcScale
AL Select
AL1
~
AL4:ON
AL1/AL2/AL3/AL4
TimeAxis
1s/div
100ms/div,1s/div,2s/div,5s/div,10s/div,
30s/div,60s/div120s/div
Set time scale of division time.
4.System
General
Brightness
5 Bright
5Bright/4/3/2/1Dark/0 Off
Off means that whole of secreen is
turned off.
PowerOnDelay
None
None/2sec/5sec/10sec/20sec/30sec/60sec
Set time that until measure after power
on.
PowerSavingTime
None
None/1min/2min/5min/10min/30min/60mi
n
Display is dark while power saving.
MeasureMode
Default
Default/Multi/WaveCompare
D-ZeroRetention
Disable
Disable/Enable
Whether remember D-Zero value or not.
Language
English
日本語
/English
Language.
DisplayDirection
Horizontal
Horizontal/Vertical
Select a direction of screen.
SettingProtect
Disable
Disable/Enable
AdjustProtect
Disable
Disable/Enable
DisplayUpdateCycle
10 sps
10 sps/ 1 sps
PatternCopy
---
Go to screen of pattern copy.
Copy settings of pattern to other pattern.
AlarmLog
SyncedAlarm
AL1
~
4:ON
AL1/AL2/AL3/AL4
RecordPos
BeforeAndAfter
BeforeAlarm/BeforeAndAfter/AfterAlarm
Overwrite
Enable
Disable/Enable
Initialize
UserDefaultSave
Save current settings as use initial values.
UserDefaultLoad
Initialize setting values to user initial values.
FactoryDefautLoad