VD300 Series Inverter User Manual
Function Parameter Table
- 61 -
P08.00
PID Command
Source
0: Function code P08.01
1: AI1
2: AI2
3: AI3(extension card)
4: HS pulse input
5: MS speed command
6: Communication setting
7: Keypad potentiometer
0
○
P08.01
PID Command Set
Value
0.0%~100.0%
50.0%
○
P08.02
PID Command
UP/DOWN Time
0.00s~100.00s
0.00S
○
P08.03
PID Feedback
Source
0: AI1
1: AI2
2: AI3 (extension card)
3: AI1-AI2
4: AI1+AI2
5: MAX (AI1, AI2)
6: MIN (AI1, AI2)
7: HS Pulse input setting
8: Communication setting
9: Internal current feedback
0
○
P08.04
PID Output Feature
Selection
0: PID output positive feature
1: PID output negative feature
0
○
P08.05
PID Feedback
Display Coefficient
0.00~655.35 (Users defined units
)
1.00
○
P08.06
Proportional Gain 1
0.00~100.00
40.0
○
P08.07
Integral Time 1
0.00: Disabled integral
0.01s~10.00s
0.50s
○
P08.08
Differential Time 1
0.000s~10.000s
0.000s
○
P08.09
Proportional Gain
2
0.00~100.00
40.00
○
P08.10
Integral Time
2
0.00: Disabled integral
0.01s~10.00s
0.50s
○
P08.11
Differential Time
2
0.000s~10.000s
0.000s
○
P08.12
PID
Parameter
Switchover Condition
0: No switchover
(Only use PID parameter 1)
1: DI terminals
2: According to deviation auto-switchover
0
○
P08.13
PID
Parameter
Switchover Deviation
1
0.0%~100.0%
20.0%
○