Communication Protocol
VD300 Series Inverter User Manual
- 174 -
CMD
03H
Bit number
10H
Output frequency high bit
xx H
Output frequency low bit
xx H
Setting frequency high bit
xx H
Setting frequency low bit
xx H
Motor run speed high bit
xx H
Motor run speed low bit
xx H
Bus voltage high bit
xx H
Bus voltage low bit
xx H
Output frequency high bit
xx H
Output frequency low bit
xx H
CRC CHK low bit
xx H
CRC CHK high bit
xx H
END
T1-T2-T3-T4
9.6.2 Command Code: 06H (0000 0110), write one word
Such as: Put 5000(1388H) (namely write-in setting frequency 50.00Hz) write to slave address 01H
inverter 3001H (communication set frequency address). The frame structure description as below:
RTU Master command information.
START
T1-T2-T3-T4
ADDR
01H
CMD
06H
Write data address high bit
30H
Write data address low bit
01H
Data content high bit
13H
Data content low bit
88H
CRC CHK low bit
DAH
CRC CHK high bit
5CH
END
T1-T2-T3-T4
RTU slave response information.
START
T1-T2-T3-T4
ADDR
01H
Содержание VD300 Series
Страница 2: ......