Communication Protocol
VD300 Series Inverter User Manual
- 180 -
01063000000946CC, and inverter returned data as: 01860443A3. And the returned data 86H stands
for wrong write-in command, 04H is communication error code stands for operation failure, because
for 3000H address, the max write-in number is 09H, exceeding its setting range.
9.6.6 Continuous Communication Data Address Parameter Read Description
VD300 series inverter supports max 16 numbers continuous address parameter data reading,
communication reading only need randomly designating starting address and the data byte numbers
from starting address. Such as reading motor run frequency when inverter is run, reading motor run
speed, output current, then communication parameter starting address is 3200H, reading data byte
number is 0005H, inverter returned run data numbered 1, 3, 5 in sequence as motor running
frequency, motor run speed, output current.