VD300 Series Inverter User Manual
Parameter Description
- 99 -
P03.13
Keypad Setting Torque
-300.0%~300.0% (rated motor current)
100.0%
○
P03.14
Torque Setting Filter
Time
0.000s~10.000s
0.100s
○
Keypad set torque: inverter output torque is directly set by keypad input. 100% corresponding to the
torque size determine by the rated motor current.
Torque set the filter time: used to set torque setting changing rate, the greater the change is slower, it
is conducive to the smooth torque, but the motor response speed can be slow down.
P03.15
Source Setting of
Frequency Upper Limit of
Forward in Torque
Control
0: Function P03.17
1: AI1
2: AI2
3: AI3 (extension card)
4: High speed Pulse input
5: Communication setting
Notes: 100% of 1~4 relative to the
maximum output frequency
0
○
P03.16
Source Setting of
Frequency Upper Limit
of Reverse in Torque
Control
0: Function code P03.18
1: AI1
2: AI2
3: AI3 (extension card)
4: High speed Pulse input
5: Communication setting
Notes: 100% of 1~4 relative to the
maximum output frequency
0
○
Used to select torque control mode forward, reverse frequency upper limit setting source.
P03.17
Frequency Upper Limit
Keypad Setting of
Forward in Torque
Control
0.00Hz~P00.07 (Max output frequency)
50.00Hz
○
P03.18
Frequency Upper Limit
Keypad setting of
Reverse in Torque
Control
0.00Hz~P00.07 (Max output frequency)
50.00Hz
○
When under torque control mode, forward/reverse upper limit frequency is set by keypad, the above
two function code separately relative to forward, reverse upper limit frequency set value.
P03.19
Electric Torque Upper
Limit Source Setting
0: Function code P03.21
1: AI1
2: AI2
3: AI3 (extension card)
4: HS pulse input
5: Communication setting
Note: Setting mode 100% of 1-4
corresponds to three times of the motor
current
0
○