VD300 Series Inverter User Manual
Parameter Description
- 109 -
4
Forward Jog (FJOG)
5
Reverse Jog (RJOG)
FJOG is jog forward run, RJOG is jog reverse run. Jog run
frequency, jog Acceleration/down time refer to the function code
P09.00, P09.01 and P09.02 description;
6
Coast to stop
In any control mode (panel control, terminal control,
communication control), inverter block output, at present motor
stop is not controlled by inverter. This method is the same as
P01.05 coast to stop described;
7
Run pause
Inverter deceleration stop, but all run parameter is in memory
state, while run it doesn’t accept start/stop signal, electric level
effective;
8
Fault reset (RESET)
Using terminal function to reset error, the same function as keypad
RESET. This function can realize long distance fault reset;
9
External fault input
When external fault signal pulse sent to inverter, inverter alarm
error Er017;
10
Frequency setting
increase (UP)
11
Frequency setting
decrease(DOWN)
By external terminal pre-set frequency to change frequency
up/down command. Setting frequency can be goes up/down;
12
Frequency UP/DOWN
setting clear
When frequency to a digital or analog given to the timing, the
terminal point move can remove terminal keyboard UP/DOWN or
UP/DOWN frequency values change by the Given frequency back
to the initial value, pulse effectively;
13
Frequency UP/DOWN
setting clear
temporary
When frequency to a digital or analog given to the timing, the
terminal can remove temporarily closed terminal keyboard
UP/DOWN or UP/DOWN frequency values change by the given
frequency back to the initial value, terminal disconnect after return
to terminal keyboard UP/DOWN or UP/DOWN frequency values
change by level effectively;
14
Acceleration/decelerat
ion time selection 1
15
Acceleration/decelerat
ion time selection 1
By 4 states of the 2 terminals, to achieve the 4 acceleration /
deceleration time selection, details see table 2;
16
MS speed terminal 1
17
MS speed terminal 2
18
MS speed terminal 3
19
MS speed terminal 4
Through the 16 states of the four terminal, realize 16 speed or 16
other instruction set, details see table 1;
20
MS speed pause
When the terminal is effective, the inverter MS speed function
temporarily failure back to the original frequency; when the
terminal failure, the inverter recover to MS speed run state;
21
Immediate DC braking
This terminal is enabled, and the inverter directly switchover to the
DC braking status;
22
Deceleration DC
braking
The terminal is enabled, slow down to stop inverter and DC
braking starting frequency, and then switchover to DC braking
state;
Содержание VD300 Series
Страница 2: ......