Parameter Description
VD300 Series Inverter User Manual
- 120 -
6
High speed pulse HDI
input value
100% corresponding HDO1 output upper limit
7
AI1 input value
0.00V~10.00V
8
AI2 input value
0.00V~10.00V (Or corresponding 0.00mA~20.00mA)
9
AI3 input
value(extension card)
0.00V~10.00V (Or corresponding 0.00mA~20.00mA)
10
Reserved
11
Count value
0~Max count value
12
Output torque
100.0% corresponding 2 times of motor rated torque
13
Output current 2
0.0A~1000.0A
14
Output voltage 2
0.0V~1000.0V
15
Slope set frequency
100.0% corresponding max output frequency
16
Communication set
value 1
Corresponding MODBUS communication set value 1
17
Communication set
value 2
Corresponding MODBUS communication set value 2
P06.11
AO1 Output Voltage
(Current) Lower Limit
0.00V~P06.13 (0.00mA~P06.13)
0.00V
○
P06.12
Corresponding Setting
Value of AO1 Voltage
Output (Current) Lower
Limit
0.0%~100.0%
0.0%
○
P06.13
AO1 Output Voltage
(Current)
Upper Limit
P06.11~10.00V (P06.11~20.00 mA)
10.00V
○
P06.14
Corresponding Setting
Value of AO1 Output
Voltage (Current) Upper
Limit
0.0%~100.0%
100.0%
○
P06.15
AO1 Output Filter Time
0.000s~10.000s
0.000s
○
P06.16
AO2 Output Voltage
(Current) Lower Limit
0.00V~P06.18 (0.00mA~P06.18)
0.00V
○
P06.17
Corresponding Setting
Value of AO2 Output
Voltage (Current) Lower
Limit
00.0%~100.0%
0.0%
○
P06.18
AO2 Output Voltage
(Current) Upper Limit
P06.16~10.00V (P06.16~20.00 MA)
10.00V
○
P06.19
Corresponding Setting
Value of AO2 Voltage
(Current) Upper Limit
0.0%~100.0%
100.0%
○